Medium-voltage switchgear systems (eg Ormazabal, Siemens)
Air-insulated switchgear system, type EA up to 24kV
The system's modular design provides clear benefits for both electricity grids operated by utilities and for industrial applications. The removable switchboard units ensure a high degree of availability, easy maintenance and fault remedying. The internal arc-resistance construction ensures optimum safety and the locked switching devices guarantee fault-free and reliable operation.
Areas of application
Air-insulated, metal-encapsulated type EA switchgear systems are ideally suited for installation in:
Areas of application
Air-insulated, metal-encapsulated type EA switchgear systems are ideally suited for installation in:
- Switchgear rooms
- Walk-in substations
- Distribution substations run by power supply companies, and
- Incoming substations in the power supply grid (with or without metering/billing)
- Industrial substations for measuring the consumption of individual plants (with or without metering/billing)
- Flexible planning
- Simple installation, assembly and commissioning
- Removable functional units
- High level of availability
- Simpler maintenance
- Simplified fault remedying
- Unproblematic expansion as grid network grows
- Internal arc-resistant system construction
- Locked switchgear devices
- Safe operation
- Compact, robust, and space-saving
| Technical Specifications | ||||
| Rated voltage Ur | kV | 12 | 24 | |
| Rated frequency fr | Hz | 50 | 50 | |
| Rated operating current Ir | For busbar | A | 630 | 630 |
| For cable branch line | A | 630 | 630 | |
| For transformer branch | A | 200 | 200 | |
| Rated insulation level | Rated short-term alternating voltage Ud | kV | 28 | 50 |
| Rated surge voltage Up | kV | 75 | 95 | |
| Rated short-term inrush current Ima | kA | 50 | 40 | |
| Rated short-term current Ik with tk = 1s | kA | 20 | 16 | |
| Rated surge current Ip | kA | 50 | 40 | |
| Ambient temperature | C° | -5 C° bis + 40 C° | ||
| Accidental arcing qualification IAC AFL; 1s | kA | 20 | 16 | |
| Ingress protection rating according to VDE 0670 Part 6 | IP3X | IP3X | ||
| Colour of doors and panels | RAL | 7035 (Light grey) | ||